CIE-H10G is a remote I/O gateway equipped with 8 digital input ports, 8 digital output ports, an RS-232 and an Ethernet interface. Each digital input port is linked to a photocoupler. The input port can monitor the equipment's ON/OFF state (maximum is 24VDC). Each digital output port is linked to a relay. Apart from ON/OFF control, the digital output port can also be controlled to generate a pulse.
CIE-H10G supports Modbus TCP protocol. You can control/monitor equipment/sensors located in remote places from a PC software, mobile app, HMI, or other Modbus TCP devices. You can use our free software/app called ModMap or any software/app that supports Modbus TCP. CIE-H10G is also equipped with an embedded web server with a preloaded web page, so you can use any web browser on a PC/smartphone to access the web page to control/monitor equipment/sensors. The web page is customizable so you can easily change the web UI if needed.
CIE-H10G allows each digital output port to be automatically controlled by a logic formula of digital input and output ports. Especially, CIE-H10G can connect directly to multiple CIE-H12G, CIE-H14G, and/or other CIE-H10G to form an I/O system called Internet Switch. The system allows the output port of a device to be controlled by input ports of other devices, and vice versa, via the Internet. CIE-H10G allows up to eight TCP connections simultaneously, enabling to monitor sensors from different HMI devices/software/apps at the same time. Besides, CIE-H10G can work simultaneously as an RS232 to Ethernet converter while serving I/O operations.
Features
- 8 digital input, 8 digital output ports
- Durable steel case
- Dry contact adapter (optional)
- Monitor & control via Modbus/TCP or Web
- Controlled by simple logic formula operating autonomously
- Web-based control over custom web page
- Can be used as Internet switch
- Free Modbus/TCP program (ModMap)
Digital Input Port | |
Number of Ports | 8 |
---|---|
Interface | Isolated by Photo-coupler (WET contact) |
Electric Parameter | ON - over DC 4.5V, OFF - under DC 1.2V |
Maximum Input Voltage | DC 24V |
|
|
Digital Output Port | |
Number of Ports | 8 |
Interface | Isolated by Relays(Type A: ON - short, OFF - open) |
Relay Capacity | 5A (DC 28V, resistive load) |
|
|
Serial Physical Interface | |
Serial Interface | 1 x RS232 Port |
RXD, TXD, RTS,CTS, DTR, DSR, GND, DCD, RI | |
± 15KV ESD Protection | |
Connector | DSUB 9-pin Male |
|
|
Serial Port Property | |
Data Rate | 300bps ~ 230,400bps |
Data Bits | 8 bits, 7 bits with parity |
Parity | None, Even, Odd, Mark, Space |
Stop Bit | 1, 2(※ a single idle bit is automatically added to every stop bit by the MCU function) |
Flow control | None, RTS/CTS, Xon/Xoff |
|
|
Ethernet Port | |
Network Interface | 10Base-T/100Base-TX Ethernet(RJ45) |
Ethernet Speed Auto Sense | |
1:1 or Cross-over Cable Auto Sense | |
|
|
Software Functions | |
Protocols | Modbus/TCP, HTTP, TCP, UDP, IPv4/IPv6 dual stack, ICMPv6/TCPv6/UDPv6 |
ICMP, ARP, DHCP, PPPoE, DNS, DDNS(Dynamic DNS) | |
Telnet, Telnet COM Port Control Option (RFC 2217) | |
Security | IP & MAC filtering - Restrict host or network |
Password for Configuring | |
I/O Control Methods | Modbus/TCP, HTTP, Serialized Modbus/TCP, Macro |
Serial-Ethernet Conversion Modes | TCP Server, TCP Client, UDP, ATC |
|
|
Indicators(LEDs) | |
System LED | PWR, STS, LINK, RXD, TXD |
I/O Port LED | DI x 8, DO x 8 |
|
|
Supplementary Software | |
ezManager | Configuration tool for Windows |
ModMap | Management tool of I/O controllers for Windows |
|
|
Dimension | |
Size | 153mm x 126mm x 32mm |
Weight | Approximately 475g |
|
|
Operating Environment | |
Input Voltage | DC 5V |
Current Consumption | 450mA typical |
Operating Temperature | -40℃ ~ +70℃ |
Storage Temperature | -40℃ ~ +85℃ |
|
|
Certificate | |
KC | Registration(KN 32, KN 35) |
CE | EMC 2014/30/EU, RoHS 2011/65/EU |
Downloads
- CIE-H10G DataSheet
- CIE-H10G User Manual
- CIE-H10G CE Certificate
- CIE-H10G Declaration of RoHS Compliance
- Dry Contact Adapter(DCA)
- Dry Contact Interface
- Sending MAC Address function
- TCP Server/Client mode
- IP Change Notification(DDNS)
- Separator function
- Telnet COM Port Control Option
- Serial cable datasheet
- Modbus/TCP Protocol
- Internet switch
- Combinations of I/O controllers
- Digital Pulse Ouput
- How to use a user's homepage
- Examples of User's HTML files
- Examples of User's HTML structure and modification
- ModMap Users' manual
- CIE-H10G Frequently Asked Questions
- [ezManager.zip]ezManager v3.3F: ezTCP management program(for Windows)
- [ezterm.zip]ezTerm v1.4A: Socket program for test
- [ezVSP_60A.zip]ezVSP v6.0A: Virtual COM port driver / [HELP]
- [ModMap_21C.zip] : HMI application for Remote I/O Gateway (Supports Modbus/TCP)